Thermal storage vs tariff
Test ice or chilled-water storage against your tariff, with bill savings kept separate from energy and carbon, and solar-hour versus overnight charging.
What this page is: one calculator that runs in your browser and stores nothing. Sources and limits are on the calculators page; for a linked 42-sheet model use the engineering toolkit.
About this tool
What it does: Compares ice or chilled-water thermal storage against your tariff, and separates bill savings from energy and carbon.
Background: Load shifting lowers cost when peak or demand charges are high, but storage adds losses and often raises total electricity use.
Benefit: Shows whether the tariff justifies storage and whether solar-hour charging beats overnight charging.
Equations, units, assumptions and limits
Units: tons, ton-h, h/day, kW/ton, $/kWh, $/kW-month, kg/kWh, ft3/ton-h.
Default assumptions: Example 1,500-ton on-peak load for 6 h, 50% shifted, 150 cooling days, ice-making 1.0 kW/ton vs 0.75 normal, 5% loss. Chillers 2,500 tons installed, 900 tons of load while charging, 30% ice-mode derate, 80% of the kW reduction on the billed peak. Prices and grid factors are samples: enter your own tariff.
Limits: Uses a typical-day average, not a measured cooling profile. Checks charging capacity with a simple derate but not hourly chiller loading; ignores demand ratchets, tariff seasons beyond the months entered and redundancy design. Solar-hour and overnight charging are compared on one boundary (ice-making plus auxiliary energy) with PV counted at its opportunity cost.
Level: screening estimate. It supports planning and prioritizing, not design, procurement or a performance guarantee. Detailed engineering by qualified local professionals is required before any project.
Charging feasibility and billed-peak check
Tariff, grid and cost assumptions (enter your own)
Optional: charge in solar hours instead of overnight
Equations: Shifted ton-h = tons × window × share. Charge ton-h = shifted ÷ (1 − loss). Added kWh/day = charge × ice kW/ton + aux kW × (charge + window h) − shifted × normal kW/ton. Charging tons needed = charge ton-h ÷ charging hours, checked against capacity × (1 − derate) − load during charging. Demand saving = calculated kW reduction × share on billed peak × charge × months. Bill saving = energy-price saving + demand saving − off-peak demand penalty − O&M. Emissions use separate on-peak and off-peak grid factors. Tariff, grid and cost values are samples. Energy, peak demand, cost and emissions are reported separately because load shifting can reduce cost without reducing consumption.
Worked example
A 1,500-ton on-peak load for 6 hours with half shifted to ice storage moves 4,500 ton-h a day. With sample tariffs ($0.18 on-peak, $0.07 off-peak, $15/kW-month for 5 months) and 80% of the calculated 503 kW reduction landing on the billed peak (402 kW), the bill falls by $41,778 a year. Charging needs about 592 tons against 850 tons free in ice mode, so it fits. If the installed chillers were only 1,000 tons, the tool would flag the design as not feasible and show no payback. But ice-making and auxiliary power raise chiller electricity by 330,276 kWh a year (65% of the shifted load), and with these grid factors emissions rise by 85 tCO₂. Installed cost is $710,526, a payback of 17.0 years. Comparing charging on one boundary (ice-making plus auxiliary energy, PV counted at its opportunity cost), charging 60% from on-site PV in solar hours costs about the same ($54,629 vs $54,777 overnight) with slightly lower emissions (256 vs 266 tCO₂), so it is not a clear win. Cost savings are not energy or carbon savings.
Planning estimate, not engineering design or professional advice. Results depend on your inputs and published factors, and are not a verified inventory, audit, guarantee of savings or net-zero claim. See the terms of use.