Heat-pump water preheater: mechanical-room heat recovery
Screen a heat-pump water preheater that recovers heat from boiler, medical-air or vacuum rooms, with fuel, electricity, cooling credit and carbon.
What this page is: one calculator that runs in your browser and stores nothing. Sources and limits are on the calculators page; for a linked 42-sheet model use the engineering toolkit.
About this tool
What it does: Screens a heat-pump water preheater that recovers heat from boiler, medical-air or medical-vacuum equipment rooms.
Background: Recovered room heat can preheat domestic water and reduce room cooling, if the room, the water system and the equipment allow it.
Benefit: Shows fuel, electricity, cost and carbon effects and lists the constraints to clear before design, including downstream final heating and water management.
Equations, units, assumptions and limits
Units: kW, h/yr, degF, gal/day, $/therm, $/kWh, kg/kWh; results in kWh, therms, kBtu, kW, $, tCO2.
Default assumptions: Example 60 kW of room heat, 50% capturable, 90 degF room, rated COP 3.0 at 68 degF and a 65 degF lift (+0.3 per 10 degF of warmer air, -0.25 per 10 degF more lift), 3,000 gal/day preheated 60 to 125 degF, 80% existing heater, 0% cooling credit. 125 degF is a preheat temperature, not a storage-temperature recommendation.
Limits: COP model is linear and generic (room air and water lift): use manufacturer data at your air and water temperatures. Reports full-load demand, duty cycle and average demand separately. Only room-air heat counts; medical-vacuum exhaust and ducted or water-cooled heat are excluded. No cooling credit unless you enter a verified coincidence share. Always requires downstream final heating, storage temperature control, recirculation and water management.
Level: screening estimate. It supports planning and prioritizing, not design, procurement or a performance guarantee. Detailed engineering by qualified local professionals is required before any project.
Optional: manufacturer performance map and representative-day coincidence check
- Required ventilation and combustion air stay intact
- Equipment clearances and service access are kept
- Medical-vacuum exhaust stays separate from the heat-recovery airstream
- Medical-air and vacuum equipment keep the cooling and operation they need
- Downstream final heating, hot-water storage temperature control and recirculation are verified. Commonly cited CDC guidance is storage at or above 140 °F and circulation at or above 120 °F, subject to your water management program, ASHRAE 188 and scald prevention
- The existing heater stays as backup and redundancy is kept
Equations: With a manufacturer table, COP is interpolated linearly between your points at the measured room air temperature (no extrapolation) and the generic model below is not used. Otherwise: COP = rated COP + change per 10 °F × (room °F − 68) ÷ 10 − COP loss per 10 °F × (water lift − rated lift) ÷ 10, limited to 1.5 to 5. Demand heat = gal/day × 8.34 × ΔT × days ÷ 3,412. Heat delivered = min(demand, captured room heat × COP ÷ (COP − 1)). Heat-pump kWh = delivered ÷ COP. Fuel saved (therms) = delivered kWh × 3.412 ÷ 100 ÷ heater efficiency. Cooling credit = heat removed from the room × share coinciding with useful cooling × kW/ton (default 0%). Hourly check (optional): for each hour, delivered heat = the lesser of (heat released × capture × COP ÷ (COP − 1)) and the hot-water heat demand for that hour, summed over 24 hours and multiplied by days per year. No storage is assumed, so surplus heat in one hour is not carried to another. Fuel factor: EPA 0.005291 tCO₂/therm. COP is a generic linear model: confirm with manufacturer data. Measured room temperature, run hours and hot-water draw give a credible answer; estimates overstate recovery.
Worked example
A plant room releases 60 kW of heat into room air for 6,000 hours a year, and a heat-pump preheater can capture half. At a measured 90 °F room and a 65 °F water lift the COP is 3.66. Preheating 3,000 gal/day from 60 to 125 °F (a preheat target, not a storage temperature) needs 173,967 kWh of heat a year, all of which the recovered heat can supply. The heat pump uses 47,532 kWh (11.3 kW at full load, a 70% duty cycle, 7.9 kW on average over operating hours), displaces 7,420 therms at an 80% efficient heater, and removes heat from the room. No cooling credit is counted by default, because it needs verified data that the room is actually being cooled while the heat pump runs. On that basis the net operating saving is $2,200 a year, emissions fall 23 tCO₂, and simple payback on $60,000 is 27 years. If all recovered heat did displace mechanical cooling (the sensitivity line), the saving would be $6,083 a year and payback 9.9 years, so the cooling coincidence is the number to verify. The conditions list (ventilation, combustion air, clearances, vacuum exhaust, downstream final heating, storage temperature and water management) comes first.
Planning estimate, not engineering design or professional advice. Results depend on your inputs and published factors, and are not a verified inventory, audit, guarantee of savings or net-zero claim. See the terms of use.