Hospital Net Zero

Chilled water plant efficiency

Plant kW per ton, COP and EER from measured power and cooling, with a read on what the number means.

What this page is: one calculator that runs in your browser and stores nothing. Sources and limits are on the calculators page; for a linked 42-sheet model use the engineering toolkit.

Chilled water plant efficiencykW/ton
About this tool

What it does: Calculates plant kW per ton, COP and EER from power, flow and delta-T.

Background: Whole-plant efficiency includes chillers, pumps and towers.

Benefit: Spots poor chilled-water performance and the value of fixing it.

Tons = GPM × ΔT ÷ 24. kW/ton = kW ÷ tons. COP = 3.517 ÷ (kW/ton). EER = 12 ÷ (kW/ton). Measure kW and flow at the same time and use a meaningful load point. Whole-plant kW/ton includes pumps and towers; chiller-only figures will read lower.

Independent planning estimate using published US government factors. Not endorsed by DOE, EPA, NREL or any agency. Not an audit or a verified inventory. See methods.