Hospital hot water, Legionella control and heat recovery

How to estimate preheat energy and why heat recovery must be designed around the building water management program.

Track 4: Hospital safety and complianceIntermediate25 minutesNot started

Review status. Draft for author review. Independent technical review pending. Educational example, not a design basis. Educational and screening material only. It supports qualified professional judgment and does not determine code compliance, replace your hospital's policies or the advice of qualified engineers, clinicians and infection-prevention staff.

1. Concept

Hospitals use large amounts of hot water, and plant rooms reject heat that could preheat it. Heat-pump water preheating is attractive, but domestic water systems also carry a Legionella risk, so any change to temperatures, storage or flow is a water safety decision as well as an energy decision.

The preheater is only the first stage. Final heating, storage temperature, circulation and the water management program stay in control of safe delivery.

2. Engineering principles

3. Code and guidance

4. Worked calculation: preheat energy

  1. Hot-water demand 3,000 gallons per day, preheated from 60 to 125 degrees F.
  2. Energy per day = 3,000 x 8.34 x (125 - 60) / 3,412 = 476.6 kWh of heat.
  3. Per year (365 days) = 173,967 kWh of heat. This is the heat the preheater would need to deliver in this example.
  4. To estimate electricity use, divide the heat by the COP at the actual room temperature and water lift. A COP of 3 would mean about one third of the heat figure in electricity.
  5. The 125 degrees F in this example is a preheat temperature, not a storage temperature recommendation.

5. Hospital scenario

A plan proposes using the medical-air compressor room heat to preheat domestic hot water. What conditions must be confirmed before the project proceeds, and who must approve changes to hot-water storage and circulation?

Discuss with your team. There is no single answer; compare your reasoning with the principles above.

6. Assessment

Five original questions with explanations. Your best score is saved on this device only.

Question 1. Energy to heat 1,000 gallons through 50 degrees F is closest to:
Question 2. A heat pump preheater mainly lowers:
Question 3. Why is the cooling credit applied only to a coincident share?
Question 4. Who controls storage and circulation temperatures in hospital hot water systems?
Question 5. As the water lift (the temperature rise) increases, the heat pump COP typically:

7. Practical output: Checklist: heat recovery for domestic hot water