Refrigerants and anesthetic gases as Scope 1 emissions

Why small gas leaks and waste can matter more than expected, and how to convert volumes into carbon.

Track 5: Energy and sustainabilityFoundation20 minutesNot started

Review status. Draft for author review. Independent technical review pending. Educational example, not a design basis. Educational and screening material only. It supports qualified professional judgment and does not determine code compliance, replace your hospital's policies or the advice of qualified engineers, clinicians and infection-prevention staff.

1. Concept

Refrigerants and inhaled anesthetic agents are greenhouse gases. A kilogram can warm the climate hundreds or thousands of times more than a kilogram of carbon dioxide. Because they are released on site, they count as Scope 1 emissions.

Reducing them does not need new technology in many cases: leak management for refrigerants, and clinically appropriate choices and waste reduction for anesthetic gases. Anesthetic choices are always clinical decisions made by clinicians.

2. Engineering principles

3. Code and guidance

4. Worked calculation: conversion of volumes to CO2e

  1. Refrigerant: charge 2,000 lb of R-134a, leak rate 8 percent, GWP 1,300 (IPCC AR5). Loss = 160 lb.
  2. tCO2e = 160 x 0.45359 / 1000 x 1,300 = 94.3 tCO2e per year.
  3. Anesthetic: 240 mL of desflurane at 1.465 g/mL and GWP 2,540 gives 240 x 1.465 x 2,540 / 1,000,000 = 0.89 tCO2e.
  4. 250 mL of sevoflurane at 1.52 g/mL and GWP 130 gives 0.049 tCO2e. The desflurane bottle is about 18 times the carbon, even with less volume.
  5. GWP values vary between sources. Use the one your reporting program requires.

5. Hospital scenario

Your hospital's carbon inventory excludes refrigerants and anesthetic gases. How would you estimate them, and how would you present the findings to clinicians so the conversation supports patient safety?

Discuss with your team. There is no single answer; compare your reasoning with the principles above.

6. Assessment

Five original questions with explanations. Your best score is saved on this device only.

Question 1. Why are refrigerant leaks counted as Scope 1?
Question 2. A system has 1,000 lb of refrigerant and a 5 percent leak rate. How many pounds are lost per year?
Question 3. Which anesthetic agent generally has the highest GWP of the common volatile agents?
Question 4. Who decides which anesthetic agent is used for a patient?
Question 5. Why must you state which GWP assessment report you used?

7. Practical output: Checklist: Scope 1 gas inventory