Psychrometrics for hospital HVAC

Read the state of air: dry bulb, humidity ratio, dew point and enthalpy, and see what a cooling coil does to moist air.

Track 2: Hospital HVAC engineeringFoundation25 minutesNot started

Review status. Draft for author review. Independent technical review pending. Educational example, not a design basis. Educational and screening material only. It supports qualified professional judgment and does not determine code compliance, replace your hospital's policies or the advice of qualified engineers, clinicians and infection-prevention staff.

1. Concept

Air is a mixture of dry air and water vapor. Almost every HVAC decision in a hospital depends on two separate questions: how warm the air is, and how much water it carries. Temperature alone does not tell you the second. Two air streams at the same temperature can hold very different amounts of moisture, and the moisture decides whether a surface can sweat, whether a coil must condense water and whether a room feels comfortable.

Psychrometrics describes the properties of moist air so that these questions can be answered with numbers. The most useful properties are the dry-bulb temperature, the humidity ratio (mass of water per mass of dry air), relative humidity, dew point, wet-bulb temperature, enthalpy and specific volume. Fixing any two independent properties at a known pressure fixes the rest, which is why a psychrometric chart can be read from two lines crossing.

Hospitals care about humidity for clinical and building reasons. Surgical and sterile areas have defined temperature and humidity ranges set by the adopted standard. Very dry air is uncomfortable and raises static and drying effects; very humid air supports microbial growth, damages materials and causes condensation on cold surfaces such as chilled-water pipes and ducts.

2. Engineering principles

3. Code and guidance

4. Worked calculation: what happens across a cooling coil

  1. Air returns to the coil at 75 F and 50 percent relative humidity. At sea level this gives a humidity ratio of 0.0092 lb/lb (65 grains/lb), a dew point of 55.1 F, an enthalpy of 28.1 Btu/lb and a specific volume of 13.68 ft3/lb.
  2. The coil cools the air to 55 F at 90 percent relative humidity. The leaving humidity ratio is 0.0083 lb/lb (58 grains/lb) and the enthalpy is 22.2 Btu/lb. The leaving temperature is below the entering dew point of 55.1 F, so the coil dehumidifies.
  3. At 10,000 cfm the mass flow of dry air is 10,000 x 60 / 13.68 = 43,862 lb/h. Moisture removed = 43,862 x (0.0092 - 0.0083) = 43 lb/h, or about 5.1 gallons per hour of condensate.
  4. Total energy removed = 43,862 x (28.1 - 22.2) = 260,437 Btu/h, about 21.7 tons. Part of this is sensible cooling and part is the latent energy of the condensed water.

5. Hospital scenario

A space is held at 72 F with a humidity limit, and the chilled-water supply temperature is raised to save chiller energy. A few weeks later the area reports rising humidity and condensation on a supply grille. Using the dew-point idea, explain what probably happened, which measurements you would take at the coil and in the space, and what would have to be reviewed before the setpoint change is repeated.

Discuss with your team. There is no single answer; compare your reasoning with the principles above.

6. Assessment

Five original questions with explanations. Your best score is saved on this device only.

Question 1. Air is heated in a duct with no moisture added. Which property stays the same?
Question 2. A pipe surface is at 52 F. The room air has a dew point of 55 F. What is expected?
Question 3. For tracking how much water a coil removes, the best property to compare is:
Question 4. Why can a higher chilled-water supply temperature reduce dehumidification?
Question 5. Two air streams are both at 75 F. One has a dew point of 45 F and the other 60 F. Which statement is correct?

7. Practical output: Verification checklist: humidity problem at a coil or in a space