Chilled water plant efficiency and delta-T
How to turn power, flow and temperature difference into tons and kW per ton, and why low delta-T quietly wastes pumping energy.
1. Concept
The chilled water plant is the largest electricity user in many hospitals. Its performance is described by kW per ton: the electrical power the whole plant uses for each ton of cooling delivered. Lower is better.
Delta-T is the difference between return and supply water temperature. When it falls below design, the same cooling needs more flow, which increases pumping energy and can force extra chillers to run.
2. Engineering principles
- Cooling delivered in tons = flow in GPM x delta-T in degrees F / 24 for water.
- Whole-plant kW per ton = total plant power (chillers, pumps, cooling towers) / tons.
- Low delta-T is often caused by control valves, dirty or bypassed coils, high supply temperatures or loop bypass, not by the chillers.
- Pump power rises steeply with flow, roughly with the cube of flow in an ideal variable-speed system, so extra flow is expensive.
- Redundancy and clinical cooling requirements limit how aggressively a plant can be shut down. Efficiency work keeps spare capacity for critical areas.
3. Code and guidance
- Cooling capacity and redundancy are set by design criteria and the hospital's own risk assessment; ventilation standards limit temperature and humidity in clinical spaces.
- Energy standards and benchmarks such as ASHRAE 90.1 and ENERGY STAR provide context but do not replace plant measurements.
4. Worked calculation: tons, kW per ton and the cost of low delta-T
- Measured: plant power 900 kW, flow 3,000 GPM, delta-T 12 degrees F.
- Tons = 3,000 x 12 / 24 = 1,500 tons.
- kW per ton = 900 / 1,500 = 0.600.
- If delta-T falls to 8 degrees F while the load stays 1,500 tons, flow must be 4,500 GPM.
- Ideal pump power then rises by (4,500 / 3,000)^3 = 3.38 times. Real systems differ, but the direction is clear: low delta-T multiplies pumping energy.
5. Hospital scenario
Your plant reports delta-T of 8 degrees F in summer against a design of 12. Three chillers are running at part load. List the likely causes and the order you would investigate them in.
Discuss with your team. There is no single answer; compare your reasoning with the principles above.
6. Assessment
Five original questions with explanations. Your best score is saved on this device only.
7. Practical output: Checklist: chilled water plant efficiency review
Related tools
Standards and references
- ASHRAE Handbook, HVAC Systems and Equipment (chilled water systems)
- ASHRAE Standard 90.1
Confirm the edition adopted for your project and jurisdiction. Standards are cited by name only; no standard text is reproduced here.