Chilled water plant efficiency and delta-T

How to turn power, flow and temperature difference into tons and kW per ton, and why low delta-T quietly wastes pumping energy.

Track 2: Hospital HVAC engineeringFoundation25 minutesNot started

Review status. Draft for author review. Independent technical review pending. Educational example, not a design basis. Educational and screening material only. It supports qualified professional judgment and does not determine code compliance, replace your hospital's policies or the advice of qualified engineers, clinicians and infection-prevention staff.

1. Concept

The chilled water plant is the largest electricity user in many hospitals. Its performance is described by kW per ton: the electrical power the whole plant uses for each ton of cooling delivered. Lower is better.

Delta-T is the difference between return and supply water temperature. When it falls below design, the same cooling needs more flow, which increases pumping energy and can force extra chillers to run.

2. Engineering principles

3. Code and guidance

4. Worked calculation: tons, kW per ton and the cost of low delta-T

  1. Measured: plant power 900 kW, flow 3,000 GPM, delta-T 12 degrees F.
  2. Tons = 3,000 x 12 / 24 = 1,500 tons.
  3. kW per ton = 900 / 1,500 = 0.600.
  4. If delta-T falls to 8 degrees F while the load stays 1,500 tons, flow must be 4,500 GPM.
  5. Ideal pump power then rises by (4,500 / 3,000)^3 = 3.38 times. Real systems differ, but the direction is clear: low delta-T multiplies pumping energy.

5. Hospital scenario

Your plant reports delta-T of 8 degrees F in summer against a design of 12. Three chillers are running at part load. List the likely causes and the order you would investigate them in.

Discuss with your team. There is no single answer; compare your reasoning with the principles above.

6. Assessment

Five original questions with explanations. Your best score is saved on this device only.

Question 1. A plant moves 2,400 GPM with a 10 degrees F delta-T. How many tons is it delivering?
Question 2. Which is the most common reason for low delta-T?
Question 3. A whole-plant efficiency figure of 0.6 kW/ton includes:
Question 4. Why is a single operating-point measurement not enough?
Question 5. Before shutting down a standby chiller to save energy, you should:

7. Practical output: Checklist: chilled water plant efficiency review

Related tools

Standards and references