Sensible, latent and coil loads
Where the 1.08, 0.68 and 4.5 factors come from, how to split a load into sensible and latent parts and how that sets airflow and coil size.
1. Concept
Every cooling load has two parts. The sensible part changes the temperature of the air. The latent part changes its moisture content. Both appear as heat the cooling system must remove, and they behave differently: sensible load is carried away by cold supply air, while latent load needs a coil cold enough to condense water.
The three common quick equations are shortcuts built from air properties at standard conditions. Each is derived from mass flow times a property change, so understanding the derivation tells you when the shortcut stops being accurate, such as at altitude, with very hot air or with unusual moisture levels.
In hospitals the split matters more than in many buildings. Ventilation rates are high, outdoor air is often humid, and space humidity must be held within a range. A coil selected for the total load only may meet the temperature but not the humidity.
2. Engineering principles
- Sensible heat: Qs = 1.08 x cfm x dT, with Qs in Btu/h and dT in F. The 1.08 equals 60 min/h x 0.075 lb/ft3 x 0.24 Btu/lb-F for standard air.
- Latent heat: Ql = 0.68 x cfm x d(grains), with d(grains) the humidity-ratio difference in grains per pound. The 0.68 comes from 60 x 0.075 x 1,050 Btu/lb / 7,000 grains per pound, using about 1,050 Btu/lb for the energy to condense water.
- Total heat: Qt = 4.5 x cfm x dh with dh the enthalpy difference in Btu/lb. The 4.5 is 60 x 0.075. It applies to the total load including both parts.
- Sensible heat ratio SHR = Qs / Qt. A low SHR means a large latent share and a coil that must run colder to dehumidify. Many hospitals with high outdoor air quantities have a lower SHR than offices.
- A room's sensible load sets its supply airflow: cfm = Qs / (1.08 x dT supply). A bigger supply temperature difference needs less air; the room's humidity then depends on the coil's leaving dew point.
3. Code and guidance
- Load calculations for design follow recognized methods published in the handbook literature and are done by qualified engineers. The shortcuts in this lesson check and explain the answers; they do not replace the method.
- Ventilation rates and the minimum outdoor air quantity for each space type come from the adopted ventilation standard. Outdoor air enters the load calculation through the factors above.
- Where you use the 1.08 factor at altitude, correct it for the lower air density, or use mass flow and enthalpy from first principles.
4. Worked calculation: coil load for a ventilation air stream
- An air handler cools 5,000 cfm of mixed air by 20 F and removes 35 grains/lb of moisture.
- Sensible load = 1.08 x 5,000 x 20 = 108,000 Btu/h.
- Latent load = 0.68 x 5,000 x 35 = 119,000 Btu/h.
- Total = 227,000 Btu/h, or 18.9 tons. SHR = 108,000 / 227,000 = 0.48. About 52 percent of the load is latent.
- A room with a sensible load of 60,000 Btu/h supplied at a 20 F temperature difference needs 60,000 / (1.08 x 20) = 2,778 cfm. If the supply difference were 15 F, the same room would need 3,704 cfm.
5. Hospital scenario
A hospital replaces a cooling coil with one sized from the sensible load only. In summer the supply air meets the temperature setpoint but the space runs humid. Explain why the sensible heat ratio matters, which factor would you use to estimate the missing latent load, and what data from the existing system would you collect.
Discuss with your team. There is no single answer; compare your reasoning with the principles above.
6. Assessment
Five original questions with explanations. Your best score is saved on this device only.
7. Practical output: Verification checklist: coil or airflow selection from loads
Related tools
Standards and references
- ASHRAE Handbook, Fundamentals (confirm the current edition)
- ASHRAE Handbook, HVAC Systems and Equipment (confirm the current edition)
- ANSI/ASHRAE/ASHE Standard 170 for space ventilation criteria (confirm adopted edition)
Confirm the edition adopted for your project and jurisdiction. Standards are cited by name only; no standard text is reproduced here.