Sensible, latent and coil loads

Where the 1.08, 0.68 and 4.5 factors come from, how to split a load into sensible and latent parts and how that sets airflow and coil size.

Track 2: Hospital HVAC engineeringFoundation25 minutesNot started

Review status. Draft for author review. Independent technical review pending. Educational example, not a design basis. Educational and screening material only. It supports qualified professional judgment and does not determine code compliance, replace your hospital's policies or the advice of qualified engineers, clinicians and infection-prevention staff.

1. Concept

Every cooling load has two parts. The sensible part changes the temperature of the air. The latent part changes its moisture content. Both appear as heat the cooling system must remove, and they behave differently: sensible load is carried away by cold supply air, while latent load needs a coil cold enough to condense water.

The three common quick equations are shortcuts built from air properties at standard conditions. Each is derived from mass flow times a property change, so understanding the derivation tells you when the shortcut stops being accurate, such as at altitude, with very hot air or with unusual moisture levels.

In hospitals the split matters more than in many buildings. Ventilation rates are high, outdoor air is often humid, and space humidity must be held within a range. A coil selected for the total load only may meet the temperature but not the humidity.

2. Engineering principles

3. Code and guidance

4. Worked calculation: coil load for a ventilation air stream

  1. An air handler cools 5,000 cfm of mixed air by 20 F and removes 35 grains/lb of moisture.
  2. Sensible load = 1.08 x 5,000 x 20 = 108,000 Btu/h.
  3. Latent load = 0.68 x 5,000 x 35 = 119,000 Btu/h.
  4. Total = 227,000 Btu/h, or 18.9 tons. SHR = 108,000 / 227,000 = 0.48. About 52 percent of the load is latent.
  5. A room with a sensible load of 60,000 Btu/h supplied at a 20 F temperature difference needs 60,000 / (1.08 x 20) = 2,778 cfm. If the supply difference were 15 F, the same room would need 3,704 cfm.

5. Hospital scenario

A hospital replaces a cooling coil with one sized from the sensible load only. In summer the supply air meets the temperature setpoint but the space runs humid. Explain why the sensible heat ratio matters, which factor would you use to estimate the missing latent load, and what data from the existing system would you collect.

Discuss with your team. There is no single answer; compare your reasoning with the principles above.

6. Assessment

Five original questions with explanations. Your best score is saved on this device only.

Question 1. What does the 1.08 factor in Qs = 1.08 x cfm x dT represent?
Question 2. A coil has Qs = 90,000 Btu/h and Ql = 60,000 Btu/h. What is the sensible heat ratio?
Question 3. Why must the 1.08 factor be corrected at high altitude?
Question 4. A space needs 120,000 Btu/h sensible cooling at a 20 F supply difference. Which airflow is closest?
Question 5. A system with a high outdoor air quantity in a humid climate will usually have:

7. Practical output: Verification checklist: coil or airflow selection from loads