Heat pumps, dedicated outdoor air and radiant cooling
Efficiency ratings and what they mean, why a dedicated outdoor air system must carry the latent load and how dew point limits chilled beams and radiant panels.
1. Concept
A heat pump moves heat instead of making it. In heating it takes heat from outdoor air, water or the ground and delivers more heat than the electricity it uses. The ratio is the coefficient of performance. In cooling the same machine rejects heat outdoors and its efficiency is described as EER, kW per ton or COP.
A dedicated outdoor air system separates two jobs. A central unit conditions and dries the ventilation air and delivers it to the zones, while local terminal equipment handles the sensible load. This works well with chilled beams and radiant panels, which cool by water and cannot remove moisture. If the room humidity rises above the surface dew point, those surfaces sweat.
In hospitals the idea is attractive because it separates ventilation from space conditioning and can reduce reheat. But it must be reconciled with infection-control rules: wet surfaces, condensate and the cleaning of terminal devices are significant concerns in patient areas, so the design needs clinical and infection-prevention review.
2. Engineering principles
- Efficiency conversions: EER = 12 / (kW per ton) and COP = EER / 3.412. A chiller at 0.6 kW/ton has an EER of 20 and a COP of about 5.9.
- Efficiency changes with conditions. A rating at full load is not the same as a seasonal or part-load figure, and heat pump heating efficiency falls as the outdoor temperature falls.
- For a DOAS the supply air must absorb the zone latent load: required drop in grains = latent load / (0.68 x cfm), so the supply air must have a humidity ratio below the room's by that amount.
- Chilled beams and radiant panels run with water above the room dew point, so the DOAS must keep the room dew point low enough that no surface sweats. Dew-point sensors and control sequences that raise the water temperature or close the water when humidity rises are standard.
- Heat pump efficiency depends on the source temperature and the temperature lift. Lowering the supply water temperature in heating and raising it in cooling improves efficiency.
3. Code and guidance
- Equipment efficiency minimums come from the energy code adopted in your jurisdiction and from applicable equipment standards. Verify the rating conditions used.
- The health care ventilation standard and infection-prevention review decide whether chilled beams, radiant surfaces and induction units are allowed in each patient care space.
- Refrigerant type and global warming potential matter for decarbonization. Review leak detection and handling requirements for the refrigerant selected.
4. Worked calculation: can the DOAS carry the zone latent load?
- A zone is held at 75 F and 50 percent relative humidity, which is 65 grains/lb and a dew point of 55.1 F.
- The zone has a latent load of 20,000 Btu/h and the DOAS delivers 2,000 cfm.
- Required moisture pickup = 20,000 / (0.68 x 2,000) = 14.7 grains/lb. The supply air must have a humidity ratio of 65 - 14.7 = 49.9 grains/lb.
- That corresponds to a supply dew point of about 48.2 F, so the DOAS coil leaving air must be at or below this dew point. A coil fed with typical chilled water must be able to reach it.
- For comparison, a chiller using 0.6 kW/ton has an EER of 20 and a COP of 5.9. If its plant is measured at 0.8 kW/ton, EER falls to 15.
5. Hospital scenario
A design team proposes chilled beams with a DOAS for a hospital outpatient wing. Describe the checks you would make: the supply dew point the DOAS must reach, the room dew point control, the risk of condensation on the beams, cleaning and infection-prevention requirements and the approvals needed.
Discuss with your team. There is no single answer; compare your reasoning with the principles above.
6. Assessment
Five original questions with explanations. Your best score is saved on this device only.
7. Practical output: Verification checklist: DOAS and radiant or beam system
Related tools
Standards and references
- ASHRAE Handbook, Fundamentals (confirm the current edition)
- ASHRAE Handbook, HVAC Systems and Equipment (confirm the current edition)
- Energy code adopted in your jurisdiction (confirm edition)
Confirm the edition adopted for your project and jurisdiction. Standards are cited by name only; no standard text is reproduced here.