Heat pumps, dedicated outdoor air and radiant cooling

Efficiency ratings and what they mean, why a dedicated outdoor air system must carry the latent load and how dew point limits chilled beams and radiant panels.

Track 2: Hospital HVAC engineeringFoundation25 minutesNot started

Review status. Draft for author review. Independent technical review pending. Educational example, not a design basis. Educational and screening material only. It supports qualified professional judgment and does not determine code compliance, replace your hospital's policies or the advice of qualified engineers, clinicians and infection-prevention staff.

1. Concept

A heat pump moves heat instead of making it. In heating it takes heat from outdoor air, water or the ground and delivers more heat than the electricity it uses. The ratio is the coefficient of performance. In cooling the same machine rejects heat outdoors and its efficiency is described as EER, kW per ton or COP.

A dedicated outdoor air system separates two jobs. A central unit conditions and dries the ventilation air and delivers it to the zones, while local terminal equipment handles the sensible load. This works well with chilled beams and radiant panels, which cool by water and cannot remove moisture. If the room humidity rises above the surface dew point, those surfaces sweat.

In hospitals the idea is attractive because it separates ventilation from space conditioning and can reduce reheat. But it must be reconciled with infection-control rules: wet surfaces, condensate and the cleaning of terminal devices are significant concerns in patient areas, so the design needs clinical and infection-prevention review.

2. Engineering principles

3. Code and guidance

4. Worked calculation: can the DOAS carry the zone latent load?

  1. A zone is held at 75 F and 50 percent relative humidity, which is 65 grains/lb and a dew point of 55.1 F.
  2. The zone has a latent load of 20,000 Btu/h and the DOAS delivers 2,000 cfm.
  3. Required moisture pickup = 20,000 / (0.68 x 2,000) = 14.7 grains/lb. The supply air must have a humidity ratio of 65 - 14.7 = 49.9 grains/lb.
  4. That corresponds to a supply dew point of about 48.2 F, so the DOAS coil leaving air must be at or below this dew point. A coil fed with typical chilled water must be able to reach it.
  5. For comparison, a chiller using 0.6 kW/ton has an EER of 20 and a COP of 5.9. If its plant is measured at 0.8 kW/ton, EER falls to 15.

5. Hospital scenario

A design team proposes chilled beams with a DOAS for a hospital outpatient wing. Describe the checks you would make: the supply dew point the DOAS must reach, the room dew point control, the risk of condensation on the beams, cleaning and infection-prevention requirements and the approvals needed.

Discuss with your team. There is no single answer; compare your reasoning with the principles above.

6. Assessment

Five original questions with explanations. Your best score is saved on this device only.

Question 1. A chiller uses 0.5 kW per ton. Its EER is:
Question 2. Why must a chilled beam system keep the room dew point low?
Question 3. In a DOAS, who carries the zone latent load?
Question 4. Why does heat pump heating efficiency fall in cold weather?
Question 5. Which concern is specific to chilled beams in patient areas?

7. Practical output: Verification checklist: DOAS and radiant or beam system