Ventilation and indoor air quality

How breathing-zone outdoor airflow is built from people and area rates, and why a shared system must supply more than the sum of its zones.

Track 2: Hospital HVAC engineeringFoundation25 minutesNot started

Review status. Draft for author review. Independent technical review pending. Educational example, not a design basis. Educational and screening material only. It supports qualified professional judgment and does not determine code compliance, replace your hospital's policies or the advice of qualified engineers, clinicians and infection-prevention staff.

1. Concept

Ventilation brings in outdoor air to dilute contaminants made by people and by the building. The amount needed depends on how many people use the space and how large it is, because people make some contaminants and building materials and furnishings make others.

A space served by its own air handler is simple: calculate the outdoor air the space needs and supply it. In a system with many zones sharing one air handler, a zone that needs a large fraction of outdoor air is short of it when the system mixes recirculated and outdoor air. The system must supply more than the sum of the zone requirements to protect that critical zone.

Hospitals have an extra layer. Patient care spaces use the health care ventilation standard, which sets total and outdoor air change rates by space type and requires pressure relationships. General commercial rates apply only to the spaces the adopted code assigns to them, such as offices and waiting areas that the health care standard does not cover.

2. Engineering principles

3. Code and guidance

4. Worked calculation: outdoor air for a two-zone shared system

  1. Two zones share a system. Patient wing A: 10 people, 1,000 ft2, Rp 6 cfm/person, Ra 0.1 cfm/ft2, primary airflow 1,200 cfm; Patient wing B: 30 people, 800 ft2, Rp 6 cfm/person, Ra 0.1 cfm/ft2, primary airflow 900 cfm. Example values only; use rates from the table adopted for your project. Ez = 1.0 for both.
  2. Breathing-zone outdoor airflow: Patient wing A 160 cfm (Zpz = 0.13); Patient wing B 260 cfm (Zpz = 0.29).
  3. Uncorrected system outdoor airflow Vou = 240 + 180 = 420 cfm (no diversity). Xs = 420 / 2,100 = 0.200.
  4. The critical zone is Patient wing B with Zd = 0.29. Ev = 1 + 0.200 - 0.29 = 0.911.
  5. Required system outdoor airflow Vot = 420 / 0.911 = 461 cfm. That is 41 cfm more than the uncorrected sum, which protects the critical zone.

5. Hospital scenario

A shared air handler serves patient rooms, a waiting area and an office suite. After a renovation the outdoor air damper is set to a fixed value. Explain which spaces fall under the health care standard and which under the general standard, how you would find the critical zone, what measurements verify the outdoor airflow and what happens to the critical zone if outdoor air is too low.

Discuss with your team. There is no single answer; compare your reasoning with the principles above.

6. Assessment

Five original questions with explanations. Your best score is saved on this device only.

Question 1. A zone has Rp 6 cfm/person, 20 people, Ra 0.10 cfm/ft2 and 1,000 ft2. What is Vbz?
Question 2. Why does a shared recirculating system need more outdoor air than the sum of its zones?
Question 3. What does a lower zone air distribution effectiveness do?
Question 4. A patient care space is covered by the health care ventilation standard. Which rates apply?
Question 5. Which action often most cheaply reduces system outdoor air demand?

7. Practical output: Verification checklist: outdoor air for a shared system

Related tools

Standards and references

Confirm the edition adopted for your project and jurisdiction. Standards are cited by name only; no standard text is reproduced here.

← Thermal comfort fundamentalsNext: Energy codes and heat recovery →