Duct design fundamentals

Size a duct run with the equal-friction idea, check velocity and noise, and see how fittings and shape change the pressure the fan must supply.

Track 2: Hospital HVAC engineeringFoundation25 minutesNot started

Review status. Draft for author review. Independent technical review pending. Educational example, not a design basis. Educational and screening material only. It supports qualified professional judgment and does not determine code compliance, replace your hospital's policies or the advice of qualified engineers, clinicians and infection-prevention staff.

1. Concept

A duct system is a pressure budget. The fan supplies pressure, and every foot of duct, every fitting, coil, filter and damper spends some of it. The designer chooses duct sizes so that the budget balances at an acceptable cost, noise level and energy use.

Smaller ducts cost less to build but have higher velocity, more friction, more noise and a higher fan energy use for the life of the system. Larger ducts do the reverse. The equal-friction method is the basic way to pick sizes: choose a friction rate, then size each section to that rate for its airflow.

In hospitals, the choice also interacts with cleanliness, access and pressure control. Ducts that serve critical rooms need space for access and filtration, and low velocity helps keep noise and pressure losses stable.

2. Engineering principles

3. Code and guidance

4. Worked calculation: size a supply main and add a fitting

  1. A supply duct carries 2,000 cfm. The designer chooses a friction rate of 0.08 in. w.c. per 100 ft for round galvanized duct (roughness 0.0003 ft, standard air).
  2. Solving the friction equation gives an exact diameter of 18.5 in. The next whole-inch size is 19 in.
  3. At 19 in., velocity is 1,016 fpm and friction is 0.071 in. w.c./100 ft. A larger duct gives a lower friction than the target, so it is on the safe side.
  4. Velocity pressure at 1,016 fpm is (1,016 / 4005)^2 = 0.064 in. w.c. An elbow with an assumed loss coefficient of 0.25 loses 0.25 x 0.064 = 0.016 in. w.c. Fittings are added to the straight-duct total for each run.
  5. For a 100 ft straight run plus two such elbows the loss is 0.071 + 2 x 0.016 = 0.103 in. w.c. (before coils, filters and dampers).

5. Hospital scenario

A renovation adds a branch to an existing hospital duct main. The existing fan is already near its limit. Describe what you would measure and calculate before approving the added branch: the available static pressure, the change in friction and velocity on the shared section, the effect on airflow to existing critical rooms and who must review the change.

Discuss with your team. There is no single answer; compare your reasoning with the principles above.

6. Assessment

Five original questions with explanations. Your best score is saved on this device only.

Question 1. What happens to friction loss if the diameter of a duct is reduced and airflow stays the same?
Question 2. The velocity pressure at 2,000 fpm is closest to:
Question 3. An equivalent diameter for a rectangular duct is based on matching:
Question 4. Which duct section normally sets the required fan static pressure?
Question 5. Why do high duct velocities matter beyond fan energy?

7. Practical output: Verification checklist: duct addition or resizing

Related tools

Standards and references

Confirm the edition adopted for your project and jurisdiction. Standards are cited by name only; no standard text is reproduced here.

← Fan and pump laws and variable-speed drivesNext: Hydronic system basics →